To access the stage programming menu press and hold the NEXT and DOWN buttons for 5 seconds, then release:

  • Use the arrow buttons to set softening then press NEXT
  • Use the arrow buttons to set dn then press NEXT
  • Use the arrow buttons to PosT then press NEXT
  • Use the arrow buttons to set the 1-backwash to 10 then press NEXT
  • Use the arrow buttons to set the 2-brine to 60 then press NEXT
  • Use the arrow buttons to set the 3-backwash to 5 then press NEXT
  • Use the arrow buttons to set the 4- rinse to 8 then press NEXT
  • Use the arrow buttons to set the 5-fill to the following value:
    • for the Wellmaster Softener use 9.5 lbs, then press NEXT
    • for an Aquatell Tannin system use 12 lbs, then press NEXT
  • Use the arrow buttons to set the capacity to 24.0 x 1000, then press NEXT
  • Use the arrow buttons to set the REGEN to the following value:
    • for the Wellmaster Softener set to AUTo, then press NEXT
    • for an Aquatell Tannin system set to oFF, then press NEXT
  • Use the arrow buttons to set Normal then press NEXT (will not appear for Wellmaster Softener)
  • Use the arrow buttons to set rELAY to oFF, then press NEXT